Section VI: Configuring Modbus Services
Page Section VI 913-623 @Rev A Modbus Services
2
Troubleshooting
Communications on
Serial Networks
The link on the Serial Settings dialog (previous
page) will open a diagnostics dialog in the WEB
interface to help troubleshoot or verify serial
communications with the building monitoring
system
The screen below will report the activity seen by the adapter on the serial
network.
The UPS Alarm Test will cause the MODBUS RTU server to simulate alarm
conditions. Select the condition of interest and press “Apply” to activate the
simulated alarm. Verify that the alarm is interpreted correctly at the BMS.
Make sure to select “
None Selected
” and press Apply to clear the alarm when
finished with installation testing.