CHLORIDE THREE-PHASE Uninterruptible Power System Owner’s Manual CP3000 Series P/N 913-537 REV D
1 DELIVERY AND STORAGE DELIVERY The goods have been checked thoroughly before dispatch. Immediately inspect upon receipt of the packaging and ensu
2 HANDLING The equipment must be kept upright at all times and handled with care. Damage may be caused if subjected to severe impact. The UPS
3 STORAGE When the UPS is not used within seven days of delivery, please pay special attention to the storage requirements. If the batteries or
4 PREPERATIONS FOR INSTALLATION ENVIRONMENTAL CONDITIONS The UPS and battery cabinets must be installed vertically, on a level and even surface. T
5 ACCESS AREA The area must have sufficient space for the installation to be carried out. Access doors must be sufficiently large to permit passa
6 FLOOR LOADING It is necessary that the floor in the chosen location be capable of supporting the weight of the UPS and battery cabinets. The
7 INSTALLATION Installation must be carried out only by qualified electricians and in conformity with the applicable safety standards. U N L E
8 UPS with standard autonomy Table 1 – SPECIFICATONS Unit UPS power rating kVA 10 15 20 DESCRIPTION kW 8 12 16 Voltage Vrms 208 480 480
9 SUGGESTED CABLE SIZES • Input and output conductors are based on NEC 310-16 for insulated copper conductors rated at 75°C in ambient temperatur
10 TERMINAL CONNECTIONS Table 3 – Recommended terminal connections table TERMINATION TERMINAL WIRE SIZE OF CLAMP TERMINATION TIGHTENING TORQUE
ii User and Operating Manual CHLORIDE 27944 N. Bradley Rd. • Libertyville • IL • 60048 Toll Free Phone 800-239-2257 • Toll Free Fax 800-833-6829 Phon
11 RECOMMENDED PROTECTION DEVICES The following table indicates the protection devices (circuit breakers or fuses), which must be install
12 ELECTRICAL CONNECTIONS In order to gain access to the electrical connections see figure 5, it is necessary to remove the lower right protection
13 UPS Top Plate (template)
14 UPS Bottom Plate (template)
15 TERMINATIONS Jumpers will be provided between the By-pass and the input connections. These jumpers should be removed if there
16 BATTERY BATTERY CONNECTIONS Connections must be carried out only by qualified electricians and in conformity with the applicable safety st
17 Optional Battery Cabinet The battery runtime can be increased by employing either one or two optional battery cabinet. Both the UPS and batte
18 Figure- 9 GCAB
19 Battery Cabinet Conduit Plate (Template)
20 OPERATION DISPLAY PANEL The control panel serves as the UPS user interface. LED’s (Light Emitting Diode) inform the user about
iii DECLARATION OF CONFORMITY The manufacturer: CHLORIDE Head office at: 27944 N. Bradley Rd. Libertyville, I
21 INDICATORS AND BUTTONS 1 2 3 4 5 6 ON BATTERY - when this LED is illuminated, the battery supplies the inverter ON BY
22 7 8 9 10 11 12 13 LCD Screen – Shows graphical and functional parameters CANCEL AUDIBLE ALARM - This button silen
23 Menu Structure
24 MENUS 1 2 3 4 ACTUAL VALUES By-pass Input UPS Output Battery D
25 5 . 6 7 8 ACTUAL VALUES By-pass Input UPS Output Batter
26 9 10 11 OR - 12 ALARM INFORMATION No Faults ... No Warnings ... Mes
27 13 14 15 16 MAIN MENU Actual Values Alarm Information Display Settings About ... Press
28 17 18 19 MAIN MENU Actual Values Alarm Information Display Settings About ... Press t
29 TABLE OF WARNINGS AND FAULTS Warnings Faults Over-temperature inverter Temperature in converter too high By-pass mains failu
30 MAINTENANCE BY-PASS SWITCH AND POWER CONTROL UNIT BREAKER The maintenance By-pass switch SW1 and the power control unit breaker CB1 ar
iv IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS THIS MANUAL CONTAINS IMPORTANT INSTRUCTIONS FOR THE CP3000 SERIES THAT SHOULD BE F
31 OPERATING MODES The UPS has four different Operating Modes: On-line Operation The UPS normally operates in this mode. The loads are supplied by
32 OPERATIONAL PROCEEDURES STARTUP PROCEDURE 1. With main disconnect off, switch SW1 to position 3 and CB1 off. 2. Turn main disconnect on.
33 COMMUNICATIONS Installation of communication card(s) The CP3000 series can be equipped with a variety of interfacing. Five interface slots h
34 Recommended Communication configuration The following table 5 describes in which different functions of each slot are compatible to the corresp
35 RAU/RLY/DVR CARD This card allows connection to the Remote Alarm Unit option. It also can be used to drive the Industrial Contact Card as seen
36 AS400 CARD The AS400 (Relay) card is equipped with a “D”-type female 9-pin connector comprising voltage-free contacts and conforming to the req
37 RS232 CARD The male 9-pos. SUB-D connector contains the RS 232 signals. Figure - 15 RS232 Card The interface COM is galvanically separated
38 ManageUPSNET CARD ManageUPSNET (formerly known as the SNMP adapter) includes a complete package allowing CP3000 SERIES to be monitored and cont
39 LIFE2000 CARD This option provides remote monitoring of the UPS, via a dedicated telephone line, to ensure maximum reliability for the duration
40 .INDUSTRIAL CONTACT CARD Figure - 18 Industrial Contact Card and Bracket The contacts are rated at 120V, 2A.
v Table of ContentsINTRODUCTION Declaration of conformity iii Safety vii Grounding the unit viii FCC compliance
41 MAINTENANCE The UPS only requires that the air filters be cleaned on periodical bases and that the area around the UPS is clean and free from d
42 PRECAUTIONS During maintenance, disconnect the battery blocks so that no more than five batteries are connected in series. (NOTE: This cannot
43 For a number of years CHLORIDE has been committed to a policy of Total Quality and today devotes a great deal of resources and energy to provid
vi Chapter 4 BATTERY Battery connections 16 Chapter 5 OPERATION Display panel 20 Indicators and buttons 21 Menu Structu
vii Safety (English) WARNING: This equipment services power from more than one source. The convenience receptacles may have voltage even when
viii CAUTION: DO NOT dispose of batteries in a fire. The battery may explode. Do not open or mutilate the battery or battery cabinet. Released elect
ix FCC Compliance ATTENTION: Changes or modifications to this unit not expressly approved by the party responsible or in FCC compliance could voi