PREPERATIONS FOR INSTALLATION
ENVIRONMENTAL CONDITIONS
The UPS and battery cabinets must be installed vertically, on a level and even surface. The UPS and battery cabinets must be
protected from extremes temperatures, water, humidity, and the presence of conductive powder or dust. Do not stack units and do
not place any objects on top of the unit. Although the functional temperature range of the UPS is 32°F to 104°F (0°C to 40°C).
The ideal environmental temperature range is 59°F to 77°F (15°C to 25°C) due to the battery life design at 77°F (25°C). Each
increment of 15°F above 77°F reduces the expected battery life by 50%. See battery manufacturer’s recommendations.